Tripp Lite SMART5000RT3U 5000VA UPS

TRIPP LITE Part #/MPN: SMART5000RT3U

DiscTech Item #: TRI-SMART5000RT3U-BN-2Y


$4,249.00
  • Low Stock:Call for ETA
    Stock Levels

    This item is currently (nearly) out of stock. It may be possible to arrange fast shipment. If you need it urgently call us. Otherwise, it usually ships within 1 week.

$4,249.00

Interface Types: Serial RS-232 DB9

U Height: 6U

Voltage: 208V

Color: Silver

Tripp Lite SmartPro SMART5000RT3U 208V & 120V 5000VA / 4000W Line Interactive Sine Wave UPS 6U Rack Tower - Brand New

Tripp Lite SmartPro SMART5000RT3U 208V & 120V 5000 VA /5kVA / 4000 Watt / 4kW USB / DB9 14 Outlet Line Interactive Sine Wave Uninterruptible Power Supply 6U (3U UPS/power module and 3U external battery pack) Rack Tower Extended Run - Brand New

Overview
Tripp Lite's line-interactive SMART5000RT3U UPS System protects server, networking or telecommunications equipment from blackouts, voltage fluctuations and surges in a compact tower/rackmount housing. In rack configuration, the power module and battery pack occupy only 3 rack spaces (3U) each. Large capacity 5000VA/4000W power module converts raw 208V AC input to fully regulated dual output 208/120 voltage for simultaneous protection of both high- and low-voltage equipment loads. True sine wave output at all times offers guaranteed compatibility with all equipment types. Includes 14 outlets, 8 of which can be individually reset via software interface to selectively reboot remote equipment or shed less critical loads to extend battery runtime for more critical equipment. Battery support can be extended indefinitely with additional external 3U rackmount battery packs. Includes slot for internal Network Management Card option. Also includes two DB9 and two USB enhanced monitoring ports for unattended shutdown, remote control and monitoring of UPS system and power data.

Features

  • Large 5000VA/4000W output capacity with full-time sine wave output offers guaranteed compatibility with all equipment types
  • High power density 5kVA power module and battery pack occupy only 3 rack spaces (3U) each (UPS and battery pack require 6U total installed)
  • 38 min. half load runtime, expandable with multiple external battery packs BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible)
  • Line-interactive voltage regulation corrects severe brownouts and overvoltages without using battery power
  • Dual voltage output is simultaneously compatible with both 208V and 120V equipment
  • 14 total outlets (120V: 10 x 5-15R, 2 x 5-20R/208V: 1 x L6-30R, 1 x L14-30R)
  • Diagnostic LEDs provide visual indication of 17 separate performance conditions
  • USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from www.tripplite.com/poweralert
  • 4 built-in communications ports (2 x DB9, 2 x USB) for remote monitoring and unattended shutdown
  • Compatible with Tripp Lite UPS management card options WEBCARDLX and SNMPWEBCARD
  • 8 customized load management receptacles can be individually powered off and back on again via software interface to reboot remote equipment or perform "load shedding" of less critical loads to extend battery runtime for the most critical equipment
  • Emergency Power Off (EPO) interface for emergency shutoff in large facilities
  • Hot-swappable/user replaceable external battery pack(s) allow on-site battery replacement without powering off connected equipment or removing the UPS from the rack
  • Intelligent battery management system extends battery life
  • Included UPS external battery pack ships fully assembled and ready for connection to the power module, no time consuming, connection of individual internal batteries by user is necessary

Package Includes

  • SMART5000RT3U UPS System
  • BP48V60RT3U battery pack
  • USB & DB9 Serial cabling
  • Mounting hardware
  • Instruction manual

UPS BATTERY BACKUP
Model NumberSMART5000RT3U
OUTPUT SPECIFICATIONS
Output Volt Amp Capacity (VA)5000
Output kVA Capacity (kVA)5
Output Watt Capacity (Watts)4000
Output kW Capacity (kW)4
Output Capacity Details Output increases to 4800W maximum when user supplied 50A input plug or hardwire input is used
Power Factor0.8
Nominal Output Voltage(s) Supported110V
115V
120V
208V
Nominal Voltage Details208/120V nominal output in battery mode
Frequency Compatibility60 Hz
Output Voltage Regulation (Line Mode)208 & 120V (-10%, +20%)
Output Voltage Regulation (Battery Mode)+/- 5%
Output Receptacles(10) 5-15R
(2) 5-15/20R
(1) L14-30R
(1) L6-30R
Load Management ReceptaclesEight switchable single-outlet 5-15R load banks
Output Circuit Breakers15A branch rated (x3) - 2 breakers support 5 5-15R outlets each, one breaker supports 2 5-20R outlets, L6-30R and L14-30R outlets are unbreakered
Output AC Waveform (AC Mode)Sine wave
Output AC Waveform (Battery Mode)Pure Sine wave
INPUT SPECIFICATIONS
Rated input current (Maximum Load)24A max. in factory L6-30P configuration; 27A max. when powered by 50A plug or hardwire input
Nominal Input Voltage(s) Supported208V AC
UPS Input COnnection TypeL6-30P
Input Circuit Breakers30A double-pole
UPS Imput Cord Length (ft.)10
Recommended Electrical Service30A 208V
Input PhaseSingle-Phase
BATTERY SPECIFICATIONS
Full Load Runtime (min.)16 min. (4000w)
Half Load Runtime (min.)28 min. (2000w)
Expandable Battery RuntimeExtended runtime supported via optional external battery packs
External Battery Pack CompatibilityBP48V24-2U(limit 1)
BP48V60RT-3U(multi-pack compatible)
BP48V27-2US(multi-pack compatible)
DC System Voltage (VDC)48
Battery Recharge Rate (Included Batteries)Less than 4 hours from 10% to 90% (typical, full load discharge)
Battery Replacement DescriptionHot-swappable, user replaceable batteries
Expandable RuntimeYes
VOLTAGE REGULATION SPECIFICATIONS
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 282
Overvoltage CorrectionInput voltages between 240V and 260 are reduced by 12%
Undervoltage CorrectionInput voltages between 180V and 199 are boosted by 12%
Severe Undervoltage CorrectionInput voltages between 151V and 179 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS SPECIFICATIONS
Switches2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel OperationPower-fail alarm can be silenced using alarm-cancel switch
nce silenced, alarm will re-sound to indicate low-battery status
Audible AlarmAudible alarm indicates UPS startup, power-failure, low-battery conditions
LED Indicators5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
SURGE / NOISE SUPPRESSION SPECIFICATIONS
UPS AC Suppression Joule Rating1020
UPS AC Suppression Response TimeInstantaneous
EMI / RFI AC Noise SuppressionYes
PHYSICAL SPECIFICATIONS
Included Mounting Accessory Description2 sets of 4 post rackmount installation accessories for included UPS and battery pack components
Installation Form Factors Supported with Included Accessories4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories2 post rackmount(2POSTRMKITHD)
Tower(2-9USTAND)
Optional Mounting Accessory Notes2 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate power module and battery pack
2-9USTAND tower kit included(supports up to 9U in tower format)
Primary Form FactorRackmount
UPS Power Module Dimensions (hwd, in.)5.2 x 17.5 x 22.5
Rack Height (U Spaces)6
Minimum Required Rack Depth (inches)29.5
UPS Power Module Weight (lbs/kg)93/42.18
UPS Dimensions DetailsIncludes 3U UPS/power module and 3U external battery pack
Cooling MethodFan
UPS Housing MaterialSteel
Minimum Required Rack Depth (mm)749
Primary UPS Height (mm)132
Primary UPS Width (mm)444
Primary UPS Depth (mm)572
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature Range+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity0 to 95%, non-condensing
Battery Mode BTU / Hr. (Full Load)1518
AC Mode Efficiency Rating (100% Load)94%
COMMUNICATIONS SPECIFICATIONS
Communications InterfaceUSB
DB9 Serial
Contact closure
Network Management CardsSNMPWEBCARD
WEBCARDLX
Network Monitoring Port DescriptionSupports detailed monitoring of UPS and site power conditions
2 USB ports, 1 DB9 serial and 1 DB9 contact closure port (4 total)
PowerAlert SoftwareFor local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
Communications CableUSB and DB9 cabling included
WatchDog CompatibilitySupports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER SPECIFICATIONS
Transfer Time2-4 milliseconds
Low Voltage Transfer to Battery Power (Setpoint)151
High Voltage Transfer to Battery Power (Setpoint)260
SPECIAL FEATURES SPECIFICATIONS
Grounding LugBack panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure)Cold-start operation supported
High Availability UPS FeaturesHot swappable batteries
CERTIFICATION SPECIFICATIONS
UPS CertificationsMeets FCC Part 15 Category A (EMI)
ROHS (Restriction of Hazardous Substances)
Tested to CSA (Canada)
Tested to NOM (Mexico)
Tested to UL1778 (USA)

Click here to view the manufacturer's item description/brochure

ROHS Compliant

Weight: 325 lb

Warranty: 2 Year Manufacturer

Brand New

Condition Levels Explained

The product is brand new.

2 Year Manufacturer Warranty

Product Warranties Explained

The product has a manufacturer warranty for the time period specified.